Connect the main contact cables
Connect the cables labeled Main (blue, red, and yellow) to the A, B, and C Main 1+2 inputs on the ACTAS Px60.
Input count: The P260+ has 3 Main Contact Inputs. The P360+ has 6 Main Contact Inputs.
Connect at each breaker pole
- Connect a black and red clamp to the top of each pole’s bushings.
- Plug the black cable into the black clamp.
- Plug the red cable labeled 1 into the red clamp.
- The red cable labeled 2 is only used if the pole has two interrupters.
During the test: Earthing must be removed on one side of the breaker pole.