Power on the ACTAS Px60.
- Select the Test tile on the touch screen to create a new job.
ACTAS Px60 · Quick start
Configure GIS timing for both-sides-grounded operation, then set up and perform SRM/DRM contact-resistance testing.
Download PDF GuidePower on the ACTAS Px60.
Select New switchgear to create a new template.
In the upper-right corner of the screen, press the + icon to create a new template.
Specify the switchgear manufacturer and model.
Select the Connections tab, then select the + button.
Select Timing under the custom list.
Select the Sensors tab and edit each sensor to I mc for A, B, and C. Select the gear symbol; the Rogowski coils can be selected from the library or configured directly to 100 mV/1 A.
While under Connections, configure additional criteria as required. Refer to step 9 in the general ACTAS Px60 Quick Start Guide.
Press the back arrow at the top-left of the screen to go back.
Select the Sensors tab and edit each sensor to I mc for A, B, and C. Select the gear symbol; the AC/DC Current Clamp can be selected from the library or configured directly to 100 mV/1 A.
Select the Analysis tab, then select Main contacts.
Select the Tests tab, then select the Contact resistance tab.
Select the template from the list to begin testing.
Once the template has been selected, tests may now be performed.
When switching between Timing and Contact Resistance (SRM & DRM), the Rogowski coils and AC/DC current clamps must be interchanged.
For Timing, note the direction of the arrow on the Rogowski coil; it should point in the direction of current flow. Once Timing is complete, remove the Rogowski coils from the GIS and install the AC/DC Current Clamps on the insulated earthing switch. On some GIS types, the clamp may not fit.
Setup complete. The GIS template is configured for both-sides-grounded timing and SRM/DRM contact-resistance testing, and can be selected to perform and save tests.