Connect the sensors
Connect the sensors to the secondary side of the current transformers and to the release coils, then connect them to ACTAS according to the configuration.
ACTAS Px60 · Quick start
Connect external sensors, configure triggers, and set the recording parameters for a First Trip test.
Connect the sensors to the secondary side of the current transformers and to the release coils, then connect them to ACTAS according to the configuration.
Under Connections, create a First Trip connection configuration. Click the First Trip connection configuration to open it.
Under Connections / Main contacts:
Set the sensors for measuring the coil currents under Connections / Sensors.
Switch to Trigger.
Apply a Signal function / Coil current trigger set with:
Switch to Tests / First Trip.
Define the parameters for the recording. To obtain an optimum test result, do not set either the pre-trigger duration or the recording duration below the basic setting of 500 ms.