Connect the measurement cables
Connect the cables labeled Voltage for voltage measurements and the cables labeled Current for current measurements.
- On the P360+, connect the cables to the inputs labeled Coil (U1, U2) and Motor (U, I).
- On the P260+, connect the cables to the inputs labeled Voltage / Coil (U) (I).
- ACTAS P360+ also offers the option of recording three voltages during a switchgear test. Two measurement inputs with a measuring range up to a maximum of 300 V and one measurement input with a measuring range up to a maximum of 500 V are provided for this purpose.
- ACTAS P260+ has one universal measurement input with a measuring range up to a maximum of 500 V.
- With P260+ and P360+, the motor current can be measured directly via a shunt integrated into the test system. The current measurement has a measuring range up to 100 A.